R13192Flame sensor (UV TRON)

Driving circuit C10807 [177 KB/PDF]

The R13192 delivers enhanced sensitivity through a new design of the photosensitive area.

Features

Detects fire from long distances (high sensitivity)
Detects only UV light without using any optical filters

Go to top

Applications

Fire detection in a building with large space
Arson surveillance
Discharge detection

Go to top

Characteristics

R13192 sensitivity

Go to top

Specifications

Spectral Response (Short) 185 nm
Spectral Response (Long) 260 nm
Electrode Material Ni
Weight 5.2 g
[Maximum Rating] Supply Voltage (DC) 420 V
[Maximum Rating] Average Discharge Current 3 mA
[Maximum Rating] Peak Current 50 mA
[Maximum Rating] Operation Ambient Temperature -20 to +125 ℃
Discharge Starting Voltage (DC) 260 V
Discharge Sustaining Voltage (DC) 185 V
Sensitivitiy Typ. 15000 min-1
Background Max. 5 min-1
Average Life 25000 h
[Recommended Operating Parameters] Supply Voltage (DC) 325±25 V
[Recommended Operating Parameters] Average Discharge Current 0.3 mA
[Recommended Operating Parameters] Quenching Time Min. 2 ms
Suitable Socket (Sold Separately) E678-9C

Go to top

Go to top

Disclaimer
 [66KB/PDF]

The save-to-list function can only work if JavaScript is turned on.

The recently viewed function can only work if JavaScript is turned on.