Checker Lamp

L9657-03

This is a dedicated UVTRON checker lamp.

It is compact and lightweight so can be installed on the equipment together with UVTRON. It also has excellent lighting proper ties, which enables easy and accurate operation checks to be performed.

Specifications

Item Description / Value Unit
Window material UV glass -
Emission wavelength range 185 to 400 nm
Characteristics
(at 25 ℃)
Discharge starting voltage (DC) Max. 260 V
Guaranteed life (*1) 1000 h
Recommended operating conditions  Input voltage (DC) 300 ±25 V
Average discharge current 150 µA
Absolute maximum rating Input voltage (DC) 600 V
Peak current (*2) 200 µA
Operating temperature range -40 ℃ to +125 ℃ -
Applicable standards Environmental standard (RoHS) EN 63000 -
Shock resistance characteristics (*3) 1000 m/s2
Weight Approx. 0.74 g
Driver circuit (sold separately) C13428 -

*1: The end of life is defined as the point when light output falls to 50 % of the initial value.

*2: Using the sensor at this value will considerably shorten the life.

*3: Value was measured at an action time of 11 ms using the IEC 60068-2-27 shock test method.

Characteristics

Emission spectrum distribution (Typ.)

Light distribution characteristics (Typ.)

Illustration of the measurement

Dimensional outline (Unit: mm)

Circuit configuration